Reference table for cable gauge and current
Note : Instruments will be working condition if the reference table is complied.
 
Make sure the wire gauge are proper for the input and output of power supply ,especially CD , CF-A and CIF-A Series . If do so ,over-heated circumstances will be avoided. The table regarding to the gauge upon different temperature is as follows.
Reference table for cable gauge and current

A.W.G.

approximated wire gauge

Temperature rating of copper conductor

60oC 75oC 85oC 90oC
Current rating (A)
14 2 mm2 20 20 25 25
12 3.5 mm2 25 25 30 30
10  5.5 mm2 30 35 40 40
8  8 mm2 40 50 55 55
6  14 mm2 55 65 70 75
4  22 mm2 70 85 95 95
3 30 mm2 85 100 110 110
2  38 mm2 95 115 125 130
1 50 mm2 110 130 145 150
0  60 mm2 125 150 165 170
00  70 mm2 145 175 190 195
000 80 mm2 165 200 215 225
0000 100 mm2 195 230 250 260
The impedance of wire is in direct ratio with its length, and depends inversely as diameter of wire. It affects output characteristics of CD-SERIES DC power supplies, CF-A SERIES and CIF-A SERIES AC power source directly. Therefore, voltage that measured from output terminal is not as same as the voltage on load. In general, potential difference can't be More than 0.5V.
Remark : To double or even trip the wire gauge when potential difference is above 0.5V.
AWG NO. Resistance in m-ohm / M (at 20oC)
22 52.8
20 33.5
18 20.96
16 13.19
14 8.30
12 5.22
10 3.277
 
FIG. A3-1 (Cable length and voltage drop)
 Condition : Voltage drop 0.5V JIS C3307 IV Cable

 