Programmable Power Distribution Unit |
Power Distribution Unit series specification
|
TO-> |
PDU10 | PDU6 | PDU2 | ||
Numbers of unit power ON | 1 ~ 10 | 1 ~ 6 | 1 ~ 2 | |
Input & Output Specification | ||||
Voltage range | 180 ~ 460VAC | |||
Nominal voltage | 15kW : 200 / 208 / 220 /
380 / 400 / 415VAC 18kW : 380 / 400 / 415VAC |
|||
Phase / Wires | 3-phase / 3 wires | |||
Frequency range | 45Hz ~ 65Hz | |||
5kW / 10kW / 15kW type (at 180V 3-phase) |
Maximum Current | 600A / Phase | 360A / Phase | 120A / Phase |
Maximum Power | 180kVA | 108kVA | 36kVA | |
6kW / 12kW / 18kW type (at 340V 3-phase) |
Maximum Current | 400A / Phase | 240A / Phase | 80A / Phase |
Maximum Power | 216kVA | 130kVA | 44kVA | |
Setting Function | ||||
Nominal voltage setting | 15kW : Selectable 200 / 208 / 220 / 380
/ 400 / 415VAC 18kW : Selectable 380 / 400 / 415VAC |
-- | ||
Frequency setting | Selectable 50Hz / 60Hz | -- | ||
Power OFF timer setting | DDD / HH / MM | -- | ||
Interlock I / O number | 1 ~ 3 | -- | ||
CO2 emission factor setting | 0.000kg / kWh ~ 9.999 kg / kWh | -- | ||
Control Function | ||||
Power ON order | The power ON order is from the last Slave unit to the Master unit. | |||
Power OFF order | The power OFF order is from the Master unit to the last Slave unit. | |||
Power ON / OFF control | Manual / Timer / Remote | -- | ||
Input Measuring Function | ||||
Voltage (L1, L2, L3) |
Range | 600V / 300V | -- | |
Resolution | 0.01V | -- | ||
Accuracy | +/- 0.2% | -- | ||
Frequency | Resolution | 0.001Hz | -- | |
Accuracy | +/- 0.2% | -- | ||
Output Measuring Function | ||||
Current (L1, L2, L3) |
Range | 600A / 300A / 60A | -- | |
Resolution | 0.01A | -- | ||
Accuracy | +/- 0.8% | -- | ||
Active Power (P) | Resolution | 0.001kW | -- | |
Accuracy | +/- 1.5% | -- | ||
Apparent Power (S) | Resolution | 0.001kVA | -- | |
Accuracy | +/- 1.5% | -- | ||
Power Factor | Resolution | 0.001 | -- | |
Accuracy | +/- 1% | -- | ||
Kilo-Watt-Hour | Resolution | 0.1 kWh | -- | |
Accuracy | +/- 1.5% | -- | ||
CO emission | Resolution | 0000.000 ~ 9999.999kg | -- | |
Accuracy | 0000.00000t ~ 9999.99999t | -- | ||
Efficiency(DC power supply output / input) | Resolution | 0.1% | -- | |
Accuracy | +/- 1.5% | -- | ||
Voltage Total Harmonic Distortion |
Resolution | 0.1% | -- | |
Accuracy | +/- 1% | -- | ||
Current Total Harmonic Distortion |
Resolution | 0.1 | -- | |
Accuracy | +/- 1% | -- | ||
Output Measuring Function | ||||
Emergency Stop | EMS button on the front panel | -- | ||
OVP | +10% of Nominal input | -- | ||
UVP | -10% of Nominal input | -- | ||
OCP | +10% of Max. input current | -- | ||
OLP | Adjustable from 18kVA to 180kVA |
Adjustable from 18kVA to 108kVA |
-- | |
Frequency | +/- 3Hz of 50Hz / 60Hz | -- | ||
Phase loss | Alarm and stop operation when any one of the phases loosen | -- | ||
Operation Indicators in the LCD display | ||||
REMOTE | REMOTE will show in the LCD display when the PDU is connected to PC |
-- | ||
KEY LOCK | KEY LOCK will show in the LCD display
when the keys are locked |
-- | ||
Error | ERR will show in the LCD display when any error occurs |
-- | ||
Digital interface - LAN | ||||
Conformity | LXI | -- | ||
Line ending character | Reception : LF , END ; Transmission : LF+END | -- | ||
External Control I / O | ||||
EMS | 1. Multiple rack cabinet EMS can be connected
in series. 2. Extendable EMS switch. |
|||
Interlock | Equipped three interlock connectors (in series). | -- | ||
General specification | ||||
Auxiliary Power Supply |
Input voltage | 180 ~ 460VAC ,Optional 480VAC for 15kW model only | ||
Frequency | 45Hz ~ 65Hz | |||
Power consumption | <=55W | <=46W | <=35W | |
Standby power | <=30W | <=30W | <=10W | |
Environmental Condition |
Operating environment | Indoor use | ||
Operating temperature | 0℃ ~ 50℃ | |||
Operating humidity | 30%rh ~ 80%rh (no condensation) Max 80%
RH up to 30℃ , linear decrease to 50% RH at 40℃ |
|||
Storage temperature | -20℃ ~ 70℃ | |||
Storage humidity | 10%rh ~ 80%rh (no condensation) | |||
Altitude | Up to 2000m | |||
Cooling method | Forced air cooling | |||
Withstanding voltage |
Primary - Chassis | DC2500V | -- | |
Primary – Secondary | DC2500V | -- | ||
Secondary - Chassis | DC2500V | -- | ||
Physical specification | ||||
Display panel | TFT LCD Touchscreen 127mm(5”- 800x480 ) | |||
Dimensions (W x H x D) | 440 x 176 x 849.6 mm | |||
Weight | 40kg | 35kg | 12kg | |
Accessories | ||||
LAN cable | 2m | |||
RS485 cable | 1pc (AWG24-2m) |