ELECTRICAL SPECIFICATIONS
- Current Range :
- 0.1 A…30 A peak
- 1 A…300 A peak
- 1 A…2000 A peak
- Signal de sortie :
- 100 mV AC/A AC (1 V to 10A)
- 10 mV AC/A AC (1 V to 100A)
- 1 mV AC/A AC (1 V to 1000A)
- Frequency range :
- dl/dt max. :
- Currents maxima :
- 1000 A continuous for a frequency ≦ 1kHz
(limitation proportional to the opposite of frequency beyond)
- 1200 A for 40 min max.
( pause between measurement > 20 min)
- Load impedance :
- Output impedance 1kHz :
- Accuracy and phase shift :
Primary current |
0.1…0.5A |
0.1…2A |
2…10A |
10…12A |
Accuracy in % of output
signal |
≦ 3% + 10 mV |
≦ 3% + 10 mV |
≦ 3% + 10 mV |
≦ 3% + 10 mV |
Phase shift |
not specified |
not specified |
≦ 15° |
≦ 15° |
Primary current |
0.1…0.5A |
5…20A |
20…100A |
100…120A |
Accuracy in % of output
signal |
≦ 2% + 5 mV |
≦ 2% + 5 mV |
≦ 2% + 5 mV |
≦ 2% + 5 mV |
Phase shift |
not specified |
≦ 15° |
≦ 10° |
≦ 5° |
Primary current |
1…50A |
50…200A |
200…1000A |
1000…1200A |
Accuracy in % of output
signal |
≦ 1% + 1mV |
≦ 1% + 1mV |
≦ 1% + 1 mV |
≦ 1% + 1 mV |
Phase shift |
not specified |
≦ 3° |
≦ 2° |
≦ 1° |
- Insertion impedance (at 50/60 Hz) :
- Range 10 A: < 10 mΩ
- Range 100 A: < 10 mΩ
- Range 1000 A: < 100 mΩ
- Ampere product x second :
- Rising time/ Falling down time :
- Working voltage :
- Common mode voltage :
- 600 V for category III and pollution level 2
- Adjacent conductor influence :
- Influence of conductor influence in the jaws
:
- ≦ 0.1% of output signal for frequencies
- ≦ 400 Hz
- Frequency influence :
- Range 10 A
- < 10% of output signal 10 Hz…1 kHz
- < 5% of output signal 1 kHz…10 kHz
- < 20% of output signal 10 kHz.....50 kHz
- < 3 dB 50 kHz…100 kHz
- Range 100 A
- < 5% of output signal 10 Hz…1 kHz
- < 3% of output signal 1 kHz…10 kHz
- < 20% of output signal 10 kHz…50 kHz
- < 3 dB 50 kHz…100 kHz
- Range 1000 A]
- < 1% of
output signal 10 Hz…1 kHz
- < 2% of
output signal 1 kHz…10 kHz
- < 10% of
output signal 10 kHz…50 kHz
- < 3 dB
50 kHz…100 kHz
- Influence of crest factor :
- <1 % of output
signal for a crest factor
- ≦ 6 with current
- Range 10 A: ≦
30 A peak(5 A rms)
- Range 100 A: ≦
300 A peak(50 A rms)
- Range 1000 A:
≦ 2000 A peak(500 A rms)
- Influence of DC current
superposed to nominal current :
- <1 % of output signal for a current≦ 30A DC
|
Mechanical specifications
- Operating temperature :
- Storage temperature :
- Influence of temperature :
- ≦ 0.15% of output signal per 10 K
- Operating humidity :
- From 0 to 85% of RH with linear decrease beyond 35˚C
- Influence of humidity :
- < 0.1% of output signal from 10% to 85% of RH
- Altitude :
- - Operating: 0…2000 m
- - Non-operating: 0…12000 m
|