DSP-WS Series Solar Array Simulator |
10kW /15kW models: | TO-> |
||||
10kW | 10kW | 15kW | 15kW | 15kW | |
DSP1000-30WS | DSP1300-23WS | DSP1050-42WS | DSP1500-30WS | DSP1950-23WS | |
Output voltage | |||||
Rated value (V1) | 0 ~ 1000V | 0 ~ 1300V | 0 ~ 1050V | 0 ~ 1500V | 0 ~ 1950V |
Settable range | 0 ~ 1050V | 0 ~ 1365V | 0 ~ 1102.5V | 0 ~ 1575V | 0 ~ 2047.5V |
Overvoltage protection (OVP) | 0% ~ 110% of rated output voltage | ||||
Voltage @Rated Current (V2) | 333.33V | 434.78V | 357.14V | 500V | 652.17V |
Programming resolution | 5 digits | ||||
Programming accuracy(*2) | +/- 0.1% of rated voltage | ||||
Meter resolution | 5 digits | ||||
Meter accuracy(*2) | +/- 0.1% of rated voltage | ||||
Line regulation(*6) | +/- 0.02% of rated voltage | ||||
Load regulation(*7) | +/- 0.05% of rated voltage | ||||
Temperature coefficient for set values | 100ppm/℃ of rated output voltage, after a 30 minutes warm-up | ||||
Ripple & noise (rms) (*3)(*4) | < 1440mVpp < 315mVrms |
<2240mVpp < 490mVrms |
< 1440mVpp < 315mVrms |
< 2160mVpp < 360mVrms |
< 2800mVpp < 540mVrms |
Full load up | <30ms | ||||
Full load down | <80ms | ||||
No load down | <5s | <6s | <10s | <5s | <6s |
Transient Response(*5) | < 1.5 ms | ||||
Remote compensation | 5V | ||||
Output current | |||||
Rated value (A1) | 0 ~ 30A | 0 ~ 23A | 0 ~ 42A | 0 ~ 30A | 0 ~ 23A |
Settable range | 0 ~ 31.5A | 0 ~ 24.15A | 0 ~ 44.1A | 0 ~ 31.5A | 0 ~ 24.15A |
Over current protection (OCP) | 0% ~ 110% of rated output current | ||||
Current @Rated Voltage (A2) | 10A | 7.69A | 14.28A | 10A | 7.69A |
Programming resolution | 5 digits | ||||
Programming accuracy(*2) | +/- 0.2% of rated current | ||||
Meter resolution | 5 digits | ||||
Meter accuracy(*2) | +/- 0.2% of rated current | ||||
Line regulation(*6) | +/- 0.05% of rated current | ||||
Load regulation(*7) | +/- 0.15% of rated current | ||||
Temperature coefficient for set values | 100ppm/℃ of rated output voltage, after a 30 minutes warm-up | ||||
Ripple & noise (rms)(*3)(*4) | 20mA | 20mA | 32mA | 24mA | 44mA |
Output power | |||||
Rated value | 0 ~ 10kW |
0 ~ 10kW |
0 ~ 15kW |
0 ~ 15kW |
0 ~ 15kW |
Settable range | 0 ~ 10200W |
0 ~ 10200W |
0 ~ 15300W |
0 ~ 15300W |
0 ~ 15300W |
Over power protection (OPP) | 0% ~ 110% of rated output power | ||||
Programming resolution | 5 digits | ||||
Programming accuracy(*2) | < 1% of rated output power | ||||
Meter resolution | 5 digits | ||||
Meter accuracy(*2) | +/- 0.5% of rated output power | ||||
Line regulation(*6) | < 0.05% of rated output power | ||||
Load regulation(*7) | < 0.75% of rated output power | ||||
Internal resistance | |||||
Adjustment range | 0 ~ 33.333 ohm | 0 ~ 56.521 ohm | 0 ~ 25.000 ohm | 0 ~ 50.000 ohm | 0 ~ 84.782 ohm |
Programming resolution | 0.001 ohm | 0.001 ohm | 0.001 ohm | 0.001 ohm | 0.001 ohm |
Programming Accuracy (*2) | <=2.3% of max. resistance | ||||
Insulation | |||||
Primary - Chassis | 2.5 kV DC | ||||
Primary - Secondary | 2.5 kV DC | ||||
Secondary - Chassis | 1500VDC | 2000VDC | 1500VDC | 2000VDC | 3000VDC |
Operating environment | Indoor use | ||||
Operating temperature | 0℃ ~ 50℃ | ||||
Operating humidity | 30%rh ~ 80%rh (no condensation) Max 80% RH up to 30℃, linear decrease to 50% RH at 40℃ | ||||
Storage temperature | -20℃ ~ 70℃ | ||||
Storage humidity | 10%rh ~ 80%rh (no condensation) | ||||
Altitude | Up to 2000m | ||||
Cooling method | Forced air cooling using the speed controlled fan | ||||
Ground polarity | Capable of Negative ground or Positive ground | ||||
Input | |||||
Nominal input rating | 200V ~ 415V 50Hz/60Hz 3-phase 3 wires , Optional 480V 50/60Hz 3-phase 4 wires | ||||
Input voltage range |
180VAC ~ 460VAC , Optional 480VAC (type:432VAC ~ 528VAC) | ||||
Input frequency range | 47Hz ~ 63Hz | ||||
Current (Maximum) | 40A / Phase (Input 3-phase 180V) | 60A / Phase (Input 3-phase 180V) | |||
Inrush current(Maximum) | 66A / Phase (Input 3-phase 460V) | 99 / Phase A (Input 3-phase 460V) | |||
Input Power (Maximum) | 12kVA | 18kVA | |||
Efficiency | 86 ~ 95% varies by model(*1) | ||||
Power Factor | 0.99 typ.(480V input) / 0.95 typ.(200V ~ 415V input) | ||||
Leak current | < 3.5 mA | ||||
Memory & Sequence | |||||
Number of memory | 3 sets (operating in front panel) | ||||
Maximum step number | 500 steps per each Sequence | ||||
Maximum Sequence number | 16 | ||||
Step time settable range | 0.001 sec ~ 999999.999 sec | ||||
Standard Interface | |||||
LAN interfaces | 1 x LXI 1.4 for communication, | ||||
J1 (Auxiliary control) | Function : Interlock , External output ON/OFF , Shut OFF , Alarm signal output, Output voltage downward signal | ||||
Optional Analog programming Interface | |||||
Status output (dry contact) | CV State, CC State , CP State , CR State , ON/OFF State | ||||
Voltage control | 0% ~ 100% of rated output voltage in the range of 0V ~ 5V or 0V ~ 10V | ||||
Voltage control accuracy(*2) | +/-0.2% | ||||
Current control | 0% ~ 100% of rated output current in the range of 0V ~ 5V or 0V ~ 10V | ||||
Current control accuracy(*2) | +/-0.2% | ||||
Power control | 0% ~ 100% of rated output current in the range of 0V ~ 5V or 0V ~ 10V | ||||
Power control accuracy(*2) | +/-0.2% | ||||
Monitoring output | 0 ~ 5V or 0 ~ 10V output for monitoring V/A/W | ||||
Monitoring accuracy (*2) | +/-0.2% | ||||
Reference output |
0 ~ 5VDC or 0 ~ 10VDC (max=5mA), selectable in MENU. | ||||
Optional RS-485 programming Interface | |||||
Baud rate | 4800/9600/19200/38400/57600/115200 | ||||
Line ending character | Cr , Lf , Cr+Lf selectable | ||||
Optional GPIB programming Interface | |||||
IEEE Std 488.2.1992 | |||||
Size and Weight | |||||
Enclosure (WxHxD) | 440 x 129 x 660 mm | ||||
Dimensions(WxHxD) | 482 x 132 x 765.1 mm | ||||
Weight (kg) | 34.8 | 34.8 | 43.6 | 43.6 | 43.6 |
DSP1000-30WS | DSP1300-23WS | DSP1050-42WS | DSP1500-30WS | DSP1950-23WS |
*1. Warranted at 0℃ ~ 50℃ of ambient temperature and warmed up more than 30 min. ,Humidity: Under 80% RH, ,with 2% ~ 100% of rated voltage, 1% ~ 100% of rated current, measured at the output terminals with local sensing. |
*2. Accuracy specifications warranted at 23℃+/- 5℃ |
*3 Ripple and Noise (rms value) Measurement bandwidth up to 300 kHz |
*4 Ripple and Noise (peak value) measurement bandwidth up to 20 MHz |
*5 Time for output voltage recover within +/-1% of rated value when load changes from 10% to 90% (Fig1) |
*6 Constant load (0 ~ 100%), Input changes between 180 ~ 264VAC or 342 ~ 460VAC |
*7 CV : Constant Input (Full input range), current
changes 10% ~ 90% CC : Constant Input (Full input range), voltage changes 10% ~ 100% CP : Constant Input (Full input range), voltage * current 10% ~ 90% |
*8 Output response UP time : Time for output voltage
rises from 10% to 90% of rated voltage. (Fig2) Output response Down time : Time for output voltage falls from 90% to 10% of rated voltage. |
*9 DSP-WR series, Internal resistance setting resolution
is 1m ohm, settable digits varies by model, for example: DSP80-188WR, settable range 0.001 ~ 0.444 DSP1500-30WR, settable range 0.01 ~ 50.00 See detail in operation manual. |
Fig1 |
Fig2 |
![]() |
![]() |
|
|||
|
|||