| DSP-WR Series Programmable DC Power Supply (CV , CC , CP) |
| 3.4kW models: | TO-> |
||
| DSP750-13WR | DSP1500-6WR | |||
| Output voltage | ||||
| Rated value (V1) | 0 ~ 750V | 0 ~ 1500V | ||
| Settable range(*9) | 0 ~ 787.5V | 0 ~ 1575V | ||
| Overvoltage protection (OVP) | 0% ~ 110% of rated output voltage | |||
| Voltage @Rated Current (V2)) | 250V | 500V | ||
| Programming resolution | 5 digits | |||
| Programming accuracy(*2) | +/- 0.1% of rated voltage | |||
| Meter resolution | 5 digits | |||
| Meter accuracy(*2) | +/- 0.1% of rated voltage | |||
| Line regulation(*6) | +/- 0.02% of rated voltage | |||
| Load regulation(*7) | +/- 0.05% of rated voltage | |||
| Temperature coefficient for set values | 100ppm/℃ of rated output voltage, after a 30 minutes warm-up | |||
| Ripple & noise (rms) (*3)(*4) | <830mVpp <196mVrms |
<2160mVpp < 510mVrms |
||
| Full load up | <30ms | |||
| Full load down | <80ms | |||
| No load down | <5s | <5s | ||
| Transient Response(*5) | < 1.5 ms | |||
| Remote compensation | 36V |
72V |
||
| Output current | ||||
| Rated value (A1) | 0 ~ 13.6A | 0 ~ 6.8A | ||
| Settable range(*10) | 0 ~ 14.28A | 0 ~ 7.14A | ||
| Over current protection (OCP) | 0% ~ 110% of rated output current | |||
| Current @Rated Voltage (A2) | 4.53A | 2.26A | ||
| Programming resolution | 5 digits | |||
| Programming accuracy(*2) | +/- 0.2% of rated current | |||
| Meter resolution | 5 digits | |||
| Meter accuracy(*2) | +/- 0.2% of rated current | |||
| Line regulation(*6) | +/- 0.05% of rated current | |||
| Load regulation(*7) | +/- 0.15% of rated current | |||
| Temperature coefficient for set values | 100ppm/℃ of rated output voltage, after a 30 minutes warm-up | |||
| Ripple & noise(*3)(*4) (with local sense)(CC Mode) | 15mA | 15mA | ||
| Output power | ||||
| Rated value | 0 ~ 3.4kW | |||
| Settable range(*9) | 0 ~ 3468W | |||
| Over power protection (OPP) | 0% ~ 110% of rated output power | |||
| Programming resolution | 5 digits | |||
| Programming accuracy(*2) | < 1% of rated output power | |||
| Meter resolution | 5 digits | |||
| Meter accuracy(*2) | +/- 0.5% of rated output power | |||
| Line regulation(*6) | < 0.05% of rated output power | |||
| Load regulation(*7) | < 0.75% of rated output power | |||
| Output Capacitance | ||||
| Output Capacitance | 50£gF | 12.5£gF | ||
| Internal resistance | ||||
| Adjustment range | 0 ~ 55.147£[ | 0 ~ 220.58£[ | ||
| Programming resolution | 0.001£[ | 0.01£[ | ||
| Programming Accuracy (*2) | <=2.3% of max. resistance | |||
| Insulation | ||||
| Primary - Chassis | 2.5 kV DC | |||
| Primary - Secondary | 2.5 kV DC | |||
| Secondary - Chassis | 1500VDC | 2000VDC | ||
| Operating environment | Indoor use | |||
| Operating temperature | 0¢J ~ 50¢J |
0¢J ~ 50¢J |
||
| Operating humidity | 30%rh ~ 80%rh (no condensation) Max 80% RH up to 30¢J, linear decrease to 50% RH at 40¢J | |||
| Storage temperature | -20℃ ~ 70℃ | |||
| Storage humidity | 10%rh ~ 80%rh (no condensation) | |||
| Altitude | Up to 2000m | |||
| Cooling method | Forced air cooling using the speed controlled fan | |||
| Ground polarity | Capable of Negative ground or Positive ground | |||
| Input | ||||
| Nominal input rating | 100V ~ 277V 50Hz/60Hz 1-phase 2 wires | |||
| Input voltage range |
85VAC ~ 305VAC 1-phase 2 wires | |||
| Input frequency range | 47Hz ~ 63Hz | |||
| Current (Max.)(Input 85V/180V) | 21A | 21A | ||
| Inrush current(Maximum) | 40A | 40A | ||
| Input Power (Maximum) | 3.75kVA | 3.75kVA | ||
| Efficiency(*15) @277Vin/3.4kW100% Vdc output | <=93.9% |
<=93.8% |
||
| Efficiency(*15) @277Vin/3.4kW 100% Vdc output | <=92.5% |
<=92.5% |
||
| Power Factor | 0.99 typ.(AC100 ~ 277 input) | |||
| Leak current | < 3.5 mA | |||
| Standard Interface | ||||
| LAN interfaces | 1 x LXI 1.6 for communication, | |||
| Optional Analog programming Interface | ||||
| Status output (dry contact) | CV State, CC State , CP State , CR State , ON/OFF State | |||
| Voltage control | 0% ~ 100% of rated output voltage in the range of 0V ~ 5V or 0V ~ 10V | |||
| Voltage control accuracy(*2) | +/-0.2% | |||
| Current control | 0% ~ 100% of rated output current in the range of 0V ~ 5V or 0V ~ 10V | |||
| Current control accuracy(*2) | +/-0.2% | |||
| Power control | 0% ~ 100% of rated output current in the range of 0V ~ 5V or 0V ~ 10V | |||
| Power control accuracy(*2) | +/-0.2% | |||
| Monitoring output | 0 ~ 5V or 0 ~ 10V output for monitoring V/A/W | |||
| Monitoring accuracy (*2) | +/-0.2% | |||
| Reference output |
0 ~ 5VDC or 0 ~ 10VDC (max=5mA), selectable in MENU. | |||
| Size and Weight | ||||
| Enclosure (WxHxD) | 430 x 44 x 528.2 mm | |||
| Total (WxHxD) | 483.6 x 44 x 612.2 mm | |||
| Package Dimensions(WxHxD) | 600 x 190 x 820 mm | |||
| Net weight (kg) | 10.8 | 10.8 | ||
| Gross weight (kg) | 15.4 | 15.4 | ||
| DSP750-13WR | DSP1500-6WR | |||
| *1) The output voltage and current ranges can be set to 105% of the rated value, but the total output will be less. The extra capacity is used to compensate for external wiring loss and cannot be used as a regular value. |
| *2) Measured at room temperature of 23±5°C. |
| *3) Ripple and Noise (rms value) Measurement bandwidth up to 300 kHz |
| *4) Ripple and Noise (peak value) measurement bandwidth up to 20 MHz |
| *5) The time for the output voltage to reach ±1% of the setting value at 10% - 90% of rated voltage, and 10% and above of rated power, with a resistance load. (Fig. 1) |
| *6) Input voltage variation between 200~277VAC with a fixed loading 1~100%. |
| *7) CV Mode:
Constant line voltage; output current variation between 10% - 90% of the
rated value. CC Mode: Constant line voltage; output voltage variation between 10% - 90% of the rated value. CP Mode: Constant line voltage; output voltage*current variation between 10% - 90% of the rated value. |
| *8) All data were measured at the output terminal with local sensing, at 2% - 100% of rated voltage, 1% - 100% of rated current, after 30 minutes warm-up, in a room at 50°C and 80% RH. |
| *9) "Rise Time" means the time from 10% to 90% of rated voltage; "Fall Time" is the time to drop from 90% to 10% of rated voltage. |
| *10) The performance will be affected the character of the external wiring for multi-unit paralleling. |
| *11) LXI interface with minimum 3ms response time. The actual response time will be affected by your network's connection quality and LAN speed. |
| *12) The information in this document is subject to change without notice and should not be construed as a commitment by iDRC. iDRC assumes no responsibility for any errors that may appear in this document. In no event shall iDRC be liable for incidental or consequential damages arising from use of this document or the software or hardware described in this document. |
| Fig1 |
Fig2 |
![]() |
![]() |
| |
|||
| |
|||
| Copyright 2026 CHYNG HONG ELECTRONIC CO., LTD. | Contact us |
|||